Table 63: Recommended Maximum Fuse, 200–240 V, Enclosure Sizes A, B, and C
Power
[kW (hp)]
SIBA Type RK1
Littelfuse
Type RK1
Ferraz
Shawmut
Type CC
Ferraz Shaw-
mut Type
RK1
(1)
Bussmann
Type
JFHR2
(2)
Littelfuse
JFHR2
Ferraz
Shawmut
JFHR2
(3)
Ferraz
Shawmut
J
1.1 (1.5)
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
FWX-10
HSJ-10
1.5 (2.0)
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
FWX-15
HSJ-15
2.2 (3.0)
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
FWX-20
HSJ-20
3.0 (4.0)
5017906-025
KLN-R-25
ATM-R-25
A2K-25-R
FWX-25
HSJ-25
3.7 (5.0)
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
FWX-30
HSJ-30
5.5–7.5
(7.5–10)
5014006-050
KLN-R-50
A2K-50-R
FWX-50
HSJ-50
11 (15)
5014006-063
KLN-R-60
A2K-60-R
FWX-60
HSJ-60
15 (20)
5014006-080
KLN-R-80
A2K-80-R
FWX-80
HSJ-80
18.5–22
(25–30)
2028220-125
KLN-R-125
A2K-125-R
FWX-125
HSJ-125
30 (40)
2028220-150
KLN-R-150
A2K-150-R
FWX-150
L25S-150
A25X-150
HSJ-150
37 (50)
2028220-200
KLN-R-200
A2K-200-R
FWX-200
L25S-200
A25X-200
HSJ-200
45 (60)
2028220-250
KLN-R-250
A2K-250-R
FWX-250
L25S-250
A25X-250
HSJ-250
1
A6KR-fuses from Ferraz Shawmut may substitute A2KR for 240 V drives.
2
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
3
A50X-fuses from Ferraz Shawmut may substitute A25X for 240 V drives.
Table 64: Recommended Maximum Fuse, 380–480 V, Enclosure Sizes A, B, and C
Power [kW (hp)]
Bussmann Type
RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1 (1.5)
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-6
LP-CC-6
1.5–2.2 (2.0–3.0)
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3.0 (4.0)
KTS-R-15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
4.0 (5.0)
KTS-R-20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5 (7.5)
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5 (10)
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11–15 (15–20)
KTS-R-40
JKS-40
JJS-40
18.5 (25)
KTS-R-50
JKS-50
JJS-50
22 (30)
KTS-R-60
JKS-60
JJS-60
30 (40)
KTS-R-80
JKS-80
JJS-80
37 (50)
KTS-R-100
JKS-100
JJS-100
45 (60)
KTS-R-125
JKS-125
JJS-125
AQ267037536117en-000101 / 130R0083 | 107Danfoss A/S © 2023.09
Specifications
VLT HVAC Drive FC 102
Operating Guide

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL