8 RS-485 Installation and Set-up
8.1.1 Overview
RS-485 is a two-wire bus interface compatible with multi-
drop network topology, that is, nodes can be connected as
a bus, or via drop cables from a common trunk line. A
total of 32 nodes can be connected to one network
segment.
Repeaters divide network segments.
NOTE
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address, across all
segments.
Terminate each segment at both ends, using either the
termination switch (S801) of the frequency converters or a
biased termination resistor network. Always use screened
twisted pair (STP) cable for bus cabling, and always follow
good common installation practice.
Low-impedance earth connection of the screen at every
node is important, including at high frequencies. Thus,
connect a large surface of the screen to earth, for example
with a cable clamp or a conductive cable gland. It may be
necessary to apply potential-equalizing cables to maintain
the same earth potential throughout the network - partic-
ularly in installations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable Screened twisted pair (STP)
Impedance
120 Ω
Cable length
Max. 1200 m (including drop lines)
Max. 500 m station-to-station
Table 8.1
8.1.2 Network Connection
Connect the frequency converter to the RS-485 network
as follows (see also diagram):
1. Connect signal wires to terminal 68 (P+) and
terminal 69 (N-) on the main control board of the
frequency converter.
2. Connect the cable screen to the cable clamps.
NOTE
Screened, twisted-pair cables are recommended in order to
reduce noise between conductors.
61 68 69
N
P
COMM. GND
130BB795.10
Illustration 8.1
8.1.3 Frequency Converter Hardware Set-
up
Use the terminator dip switch on the main control board
of the frequency converter to terminate the RS-485 bus.
130BB966.10
Illustration 8.2 Terminator Switch Factory Setting
The factory setting for the dip switch is OFF.
RS-485 Installation and Set...
VLT
®
Micro Drive FC 51 Design Guide
70 MG02K202 - VLT
®
is a registered Danfoss trademark
88
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Table of Contents

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)