D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 115 -
When necessary, the controller may be manually reset by holding the STOP button pressed for 30
seconds.
The manual reset will cause the hardware to be configured following new settings.
It is advised to proceed to a manual reset or power off/on cycle after every hardware configuration
modification.
The controller offers the capability of automatically determining the connection topology and setting the
voltage checks in accordance.
Related parameters are:
Automatic Topology
Detection
-
0
1
0
If this parameter is enabled, when the
engine runs, the controller will detect
the connection topology automatically
and will select alarm levels accordingly.
0: auto detect not enabled
1: auto detect enabled
If the automatic topology determination is activated by program parameter, when the engine runs, the
connection topology is tested to be one of below ones during “holdoff timer” period.
If below voltage conditions are met continuously during 3 seconds, then the topology is considered to be
determined.
If the topology cannot be determined during holdoff timer duration, then an “Unknown Topology
loaddump is generated, and the engine stops after cooldown.
This feature is especially useful for manual voltage adjustment after a new topology selection.
Available topologies to be determined are:
TOPOLOGY
Voltage
Overcurrent Limit
Overload Limit
High Wye
314V > L1&L2&L3 > 182V
Overcurrent limit x1
Overload limit x 1
Low Wye
157 V > L1&L2&L3 > 92 V
Overcurrent limit x2
Overload limit x 1
High Zigzag
276 V > L1&L2 > 204 V
Overcurrent limit x1
Overload limit x 2/3
Low Zigzag
136 V > L1&L2 > 84 V
Overcurrent limit x2
Overload limit x 2/3
During topology determination phase, if the RUN button is held
pressed, the holdoff timer will not expire and the controller will
try to determine the topology as long as the RUN button is held
pressed.
25.23. AUTOMATIC CONNECTION TOPOLOGY DETERMINATION
25.22. RESETTING THE CONTROLLER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Datakom D-100 MK2 and is the answer not in the manual?

Datakom D-100 MK2 Specifications

General IconGeneral
BrandDatakom
ModelD-100 MK2
CategoryController
LanguageEnglish

Related product manuals