D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 82 -
The unit has 3 analog sender inputs. Only parameters of one sender are explained below. Other senders
have identical parameter set.
Each sender has 16 step programmable curves. The sender name and reading unit is freely
programmable, thus the sender can be adapted to any type through programming.
Each sender has below programmable parameters:
Selects between predefined sender
functions. If this parameter is set to 13-
14-15 then the sender name string can
be freely entered.
1: on engine running
2: after hold-off timer
3: reserved
If sender resistor is above 5000 ohms,
a fault case is generated. This
parameter defines the action taken
upon fault case.
0: no alarm
1: shutdown alarm
2: loaddump alarm
3: warning
The low alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
0: low value alarm disabled
1: low value alarm enabled
0: low value warning disabled
1: low value warning enabled
The high alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
0: high value alarm disabled
1: high value alarm enabled
High Warning Check
Enable
0: high value warning disabled
1: high value warning enabled
If enabled, defines the low alarm limit.
The low alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
If defined, defines the low warning.
If enabled, defines the high alarm limit.
The high alarm may be selected as
shutdown or loaddump with “alarm
level” parameter.
If defined, defines the high warning.
16.7. SENDER CONFIGURATION