EasyManua.ls Logo

Datakom D-100 MK2 - Non-Visual Warnings

Datakom D-100 MK2
123 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 61 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
79
335
591
SERVICE-2 REQUEST:
Set if at least one of the service-2 counters has expired.
In order to reset the service counters please hold pressed
both and buttons during 5 seconds. The screen
will display “Completed!”
80
336
592
SERVICE-3 REQUEST:
Set if at least one of the service-3 counters has expired.
In order to reset the service counters please hold pressed
both and buttons during 5 seconds. The screen
will display “Completed!”
81
337
593
ENGINE RUNNING:
Set if the engine is running while the fuel output is not
energized.
82
338
594
AUTO NOT READY:
Set if the genset is not in AUTO mode or a fault condition
or the weekly schedule prevents the automatic starting of
the genset.
FUEL THEFT
Engine is not running:
If the fuel level measured from the sender input falls by 20% or more in
one hour, then Fuel Theft warning occurs (the detection delay is 10 sec,
not adjustable).
Engine is running:
If the fuel level measured from the sender input falls by 2x”hourly fuel
consumption percentage” or more, then Fuel Theft warning occurs.
FUEL FILLING
If the fuel level measured from the sender input is increased by 20% or
more in one hour, then Fuel Filling non-visual warning occurs (the
detection delay is 10 seconds, not adjustable).
MAINTENANCE DONE
Sent when the periodic maintenance counters are manually reset.
These warnings are not announced at the device front panel,
however they appear in event logs, transferred to the Scada and
cause SMS sending.
13.4. NON-VISUAL WARNINGS

Table of Contents

Related product manuals