D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 60 -
Set if no information has been received during Message
Absence Timer from the ECU of the electronic engine.
This fault condition is only controlled when fuel is on.
Set if at least one of the genset phase currents goes over
the Overcurrent Limit for the period allowed by the IDMT
curve setting. The allowed timer is dependent of the
overcurrent level. If currents go below the limit before
expiration of the timer then no alarm will be set. Please
check chapter Overcurrent Protection (IDMT) for more
details.
Set if the genset power (kW) supplied to the load goes over
the Overload limit for Overload Timer. If the power goes
below the limit before expiration of the timer then no alarm
will be set.
Set if the genset power (kW) is negative and goes over the
Reverse Power limit for Reverse Power Timer. If the
power goes below the limit before expiration of the timer
then no alarm will be set.
Set if the fault is enabled and the genset phase order is
reverse.
Set if the fault is enabled and the mains phase order is
reverse.
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
GENSET CB FAIL TO OPEN:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
Set if at least one of the service-1 counters has expired.
In order to reset the service counters please hold pressed
both and buttons during 5 seconds. The screen
will display “Completed!”