D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 60 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
68
324
580
J1939 ECU FAIL:
Set if no information has been received during Message
Absence Timer from the ECU of the electronic engine.
This fault condition is only controlled when fuel is on.
69
325
581
OVERCURRENT:
Set if at least one of the genset phase currents goes over
the Overcurrent Limit for the period allowed by the IDMT
curve setting. The allowed timer is dependent of the
overcurrent level. If currents go below the limit before
expiration of the timer then no alarm will be set. Please
check chapter Overcurrent Protection (IDMT) for more
details.
70
326
582
OVERLOAD:
Set if the genset power (kW) supplied to the load goes over
the Overload limit for Overload Timer. If the power goes
below the limit before expiration of the timer then no alarm
will be set.
71
327
583
REVERSE POWER:
Set if the genset power (kW) is negative and goes over the
Reverse Power limit for Reverse Power Timer. If the
power goes below the limit before expiration of the timer
then no alarm will be set.
72
328
584
GENSET PHASE ORDER FAIL:
Set if the fault is enabled and the genset phase order is
reverse.
73
329
585
MAINS PHASE ORDER FAIL:
Set if the fault is enabled and the mains phase order is
reverse.
74
330
586
GENSET CB FAIL TO CLOSE:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
75
331
587
GENSET CB FAIL TO OPEN:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
76
332
588
MAINS CB FAIL TO CLOSE:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
77
333
589
MAINS CB FAIL TO OPEN:
Set if the feedback input is defined and the related
contactor block feedback signal is not detected after the
expiration of Contactor Open/Close Fail Timer.
78
334
590
SERVICE-1 REQUEST:
Set if at least one of the service-1 counters has expired.
In order to reset the service counters please hold pressed
both and buttons during 5 seconds. The screen
will display “Completed!”