D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 65 -
This parameter is used to set LCD
contrast. Adjust for the best viewing
angle.
This parameter defines the delay after
the engine runs and before the fault
monitoring is enabled.
This is the period during which the
ALARM relay is active. If the period is
set to 0, this will mean that the period is
unlimited.
004-Emergency Backup
Operation
0: In RUN mode, the load will not be
transferred to the genset even if the
mains fails.
1: In RUN mode, the load will be
transferred to the genset if the mains
fails.
0: exercise once per week
1: exercise once per month
The exact exerciser day and time is
adjusted within the EXERCISE
SCHEDULE section.
008-Delayed Simulate
Mains
0: delayed simulate mains disabled
1: delayed simulate mains enabled
010-GPRS Connection
Enable
011-Rainbow Scada
Refresh Rate
The unit will update the distant
monitoring terminal with this rate.
This is the port number of the first
monitoring terminal address.
This is the port number of the second
monitoring terminal address.
This is the modbus controller identity
used in Modbus communication.
015-Oil Pressure Switch
Priority
0: crank cut is performed through oil
pressure switch and oil pressure sender
reading
1: crank cut is performed only through
oil pressure switch
016-Flashing Relay ON
Timer
Delayed Simulate Mains Operation:
max genset running time after Simulate
Mains signal disappears.
Dual Genset Systems: flashing relay
ON state duration timer.
017-Flashing Relay OFF
Timer
Dual Genset Systems: flashing relay
OFF state duration.
16. PROGRAM PARAMETER LIST