D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 66 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
018-Hysteresis Voltage
V-AC
0
30
8
This parameter provides the mains and
genset voltage limits with a hysteresis
feature in order to prevent faulty
decisions.
For example, when the mains are
present, the mains voltage low limit will
be used as the programmed low limit.
When the mains fail, the low limit will be
incremented by this value. It is advised
to set this value to 8 volts.
019-Engine Control Only
-
0
1
0
0: Genset control
1: Engine control (no alternator)
020-Alternator Pole Pairs
-
1
8
2
This parameter is used for frequency to
rpm conversion. For a 1500/1800 rpm
engine select 2. For a 3000/3600 rpm
engine select 1.
021-SMS on Mains
Change
-
0
1
0
This parameter controls SMS sending
when mains voltages status is changed.
No warnings generated.
0: no SMS on mains failed or restored
1: SMS sent on mains failed or restored
022-SMS on IP Change
-
0
1
0
This parameter controls SMS sending
when IP address of GPRS connection is
changed. No warnings generated.
0: no SMS on IP change
1: SMS sent on IP change
023-Fuel Pump Low Limit
%
0
100
20
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
024-Fuel Pump High
Limit
%
0
100
80
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
025-Warning Before Start
-
0
1
1
This parameter controls the activation of
the ALARM output during “Engine Start
Delay” timer before engine run.
0: no warning before start
1: warning before start
026-Latch all Warnings
-
0
1
0
0: warnings are latching/non-latching on
parameter control
1: all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
027-Remote Control
Enable
-
0
1
1
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0: remote control disabled
1: remote control enabled
028-CT Location
-
Gen
Load
Gen
0: CTs are at the genset side. Mains
currents are not measured.
1: CTs are at load side. Both mains and
genset currents are monitored following
contactor status.