D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 67 -
This parameter is useful to invert all CT
polarities at the same time.
0: normal CT polarity assumed.
1: reverse CT polarity assumed.
0: AMF functionality. The unit controls
both engine and load transfer. The
genset starts based on mains status.
1: ATS functionality. The unit controls
the load transfer and issues genset start
signal based on mains status.
2: REMOTE START functionality. The
unit controls engine and alternator. The
genset starts with external signal.
3: RESERVED. Not used.
031-Change Level-1
Password
Level-1 password may be modified with
this parameter
032-Change Level-2
Password
Level-2 password may be modified with
this parameter
033-LCD Backlight
Dimming Delay
If no button is pressed during this
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
After activation of the fuel pump
function, if the Fuel Pump High Limit
level is not reached, then the fuel pump
will stop for safety.
If this parameter is set to zero, then the
timer is unlimited.
0: The unit powers up in STOP mode
1: The unit powers up in the same
operating mode before power down.
If this parameter is not zero, the unit will
activate the Wait Before Transfer output
function during this timer, before
initiating a load transfer.
This function is designed for elevator
systems, in order to bring the cabin to a
floor and open doors before transfer.
037-Enable Auto not
Ready Warning
0: Auto not Ready Warning disabled
1: Auto not Ready Warning enabled
038-SMS on Engine
Run/Stop
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0: no SMS on engine run/stop
1: SMS sent on engine run/stop
039-Dual Genset Equal
Aging Enabled
0: Equal aging not enabled
041-Maintenance Done
Warning Enable
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS will be sent, the warning will be
visible on the central monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled