D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 68 -
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
043-GSM Location
Information
0: no location information from GSM
1: location information read from GSM
system.
044-Disable STOP at
Loaddump
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
period.
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
045-Current Transformer
Ratio
This is the primary/secondary ratio of
current transformers. All transformers
must have the same ratio.
046-Voltage Transformer
Ratio
This is the voltage transformer ratio.
This value will multiply all voltage and
power readings. If transformers are not
used, the ratio should be set to 1.0
The nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
The nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
When secondary voltage is selected,
this is the nominal value of genset and
mains voltages. Voltage limits are
defined by reference to this value.
When secondary frequency is selected,
this is nominal value of genset and
mains frequency. Frequency limits are
defined by reference to this value.
When tertiary voltage is selected, this is
the nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
When tertiary frequency is selected, this
is nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
053-Mains Voltage Low
Limit
If one of the mains phases goes under
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO mode. The value is defined with
reference to Nominal Voltage.
054-Mains Voltage High
Limit
If one of the mains phases goes over
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO mode. The value is defined with
reference to Nominal Voltage.
055-Mains Voltage Fail
Timer
If at least one of the mains phase
voltages goes outside of the limits
during this timer, it means that the
mains are off and it starts the transfer to
the genset in AUTO mode.