EasyManua.ls Logo

Datakom D-100 MK2 - Page 68

Datakom D-100 MK2
123 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 68 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
042-Time Zone
min
-720
+720
0
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
043-GSM Location
Information
-
0
1
0
0: no location information from GSM
1: location information read from GSM
system.
044-Disable STOP at
Loaddump
-
0
1
0
0: When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
period.
1: When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
045-Current Transformer
Ratio
-
1
1000
100
This is the primary/secondary ratio of
current transformers. All transformers
must have the same ratio.
046-Voltage Transformer
Ratio
-
0
5000
1.0
This is the voltage transformer ratio.
This value will multiply all voltage and
power readings. If transformers are not
used, the ratio should be set to 1.0
047-Nominal Voltage
V-AC
0
300
230
The nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
048-Nominal Frequency
Hz
0
500
50
The nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
049-Nominal Voltage-2
V-AC
0
300
120
When secondary voltage is selected,
this is the nominal value of genset and
mains voltages. Voltage limits are
defined by reference to this value.
050-Nominal Frequency-
2
Hz
0
500
60
When secondary frequency is selected,
this is nominal value of genset and
mains frequency. Frequency limits are
defined by reference to this value.
051-Nominal Voltage-3
V-AC
0
300
120
When tertiary voltage is selected, this is
the nominal value of genset and mains
voltages. Voltage limits are defined by
reference to this value.
052-Nominal Frequency-
3
Hz
0
500
60
When tertiary frequency is selected, this
is nominal value of genset and mains
frequency. Frequency limits are defined
by reference to this value.
053-Mains Voltage Low
Limit
%
V-100
V+100
V-20%
If one of the mains phases goes under
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO mode. The value is defined with
reference to Nominal Voltage.
054-Mains Voltage High
Limit
%
V-100
V+100
V+20%
If one of the mains phases goes over
this limit, it means that the mains are off
and starts the transfer to the genset in
AUTO mode. The value is defined with
reference to Nominal Voltage.
055-Mains Voltage Fail
Timer
sec
0
10
1
If at least one of the mains phase
voltages goes outside of the limits
during this timer, it means that the
mains are off and it starts the transfer to
the genset in AUTO mode.

Table of Contents

Related product manuals