D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 59 -
Set if the oil pressure value measured from the sender is
above the programmed limit. Warning and shutdown limits
are independently programmable. This fault will be
monitored Holdoff Timer delay after the engine is running.
Set if the coolant temperature value measured from the
sender is below the programmed limit. Warning and
shutdown limits are independently programmable.
HIGH COOLANT TEMPERATURE:
Set if the coolant temperature value measured from the
sender is above the programmed limit. Warning and
shutdown limits are independently programmable.
Set if the fuel level value measured from the sender is
below the programmed limit. Warning and shutdown limits
are independently programmable.
Set if the fuel level value measured from the sender is
above the programmed limit. Warning and shutdown limits
are independently programmable.
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
Set if the resistor value read from the sender input is
above 5000 ohms or if the terminal is left open.
Set if the genset battery voltage is below programmed
limits. Shutdown and warning limits are independently
programmable. The detection delay is also programmable.
HIGH BATTERY VOLTAGE:
Set if the genset battery voltage is above programmed
limits. Shutdown and warning limits are independently
programmable. The detection delay is also programmable.
Set if the engine is not running after programmed number
of start attempts.
Set if the engine has not stopped before the expiration of
the Stop Timer.
Set if the charge alternator voltage is below the
programmed limit. This fault will be monitored with Fault
Holdoff Timer delay after the engine is running.