D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 58 -
ALARM #
LOADDUMP#
WARNING#
DESCRIPTION
0-47
256-303
512-559
DIGITAL INPUT ALARM:
Alarm becomes active when a fault is detected from the
related digital input. Digital inputs are programmable for
the switching polarity, NO/NC contact, latching and
detection delay.
48
304
560
GENSET LOW FREQUENCY:
Set if the generator frequency is below programmed limits.
The fault will be monitored Fault Holdoff Timer delay after
the engine is running. Shutdown and warning limits are
independently programmable. The detection delay is also
programmable.
49
305
561
GENSET HIGH FREQUENCY:
Set if the generator frequency is above programmed limits.
The fault will be monitored Fault Holdoff Timer delay after
the engine is running. Shutdown and warning limits are
independently programmable. The detection delay is also
programmable. Another high frequency shutdown limit
which is 12% above the high limit is always monitored and
stops the engine immediately.
50
306
562
ENGINE LOW RPM:
Set if the engine rpm is below programmed limits. The
faults will be monitored Fault Holdoff Timer delay after the
engine is running. Shutdown and warning limits are
independently programmable. The detection delay is also
programmable. The high rpm overshoot limit is always
monitored and stops the engine immediately.
51
307
563
ENGINE HIGH RPM:
Set if the engine rpm is above programmed limits. The
faults will be monitored Fault Holdoff Timer delay after the
engine is running. Shutdown and warning limits are
independently programmable. The detection delay is also
programmable. The high rpm overshoot limit is always
monitored and stops the engine immediately.
52
308
564
GENSET LOW VOLTAGE:
Set if any of the generator phase voltages goes below
programmed limits for Voltage Fail Timer. This fault will be
monitored with Fault Holdoff Timer delay after the engine
is running.
53
309
565
GENSET HIGH VOLTAGE:
Set if any of the generator phase voltages goes above
programmed limits for Voltage Fail Timer. This fault will be
monitored with Fault Holdoff Timer delay after the engine
is running.
54
310
566
LOW OIL PRESSURE:
Set if the oil pressure value measured from the sender is
below the programmed limit. Warning and shutdown limits
are independently programmable. This fault will be
monitored Holdoff Timer delay after the engine is running.