D-100 MK2 User Manual Firmware V-6.3
K96D01-EN - 79 -
This parameter adjusts the speed of an
ECU controlled engine by +/- 8%.
172-Battery Charge Run
Voltage
If the battery voltage goes below this
limit the engine will be automatically
started in order to charge the battery
using the charge alternator.
173-Battery Charge Run
Timer
If the battery voltage goes below the
Battery Charge Run Voltage limit, the
engine will be automatically run during
this period in order to charge the battery
using the charge alternator.
174-J1939 Message
Suspand Timer
After a crank start, messages coming
from the ECU are ignored during this
timer.
175-J1939 Message
Absence Timer
If no message is received from the ECU
during this timer, then an ECU Fail
Alarm is generated.
176-Oil Pump Stop
Pressure
The oil pump is activated prior to the
crank cycle and stopped when this
pressure level is reached.
If this value is set to zero, then the oil
pump is not activated.
177-Disable ECU speed
control
0: Engine speeed checking is
performed with the RPM information
coming from the engine ECU unit.
1: the RPM information coming from the
engine ECU unit is not used for engine
speed checking.
The SPN number written to this
parameter is excuded from engine ECU
alarm list.
The FMI number written to this
parameter is excuded from engine ECU
alarm list
For Volvo engines, when this parameter
is set to 1, then the speed of the engine
is switched between 1500 and 1800
rpm.
Current day of the month.
Last two digits of the current year.
Current minute of the hour.
Current second of the minute.