Configure > Parameters > Protection(s)
Generator > Power protections Reverse power
Busbar > Voltage protections Over-voltage, Under-voltage
Busbar > Frequency protections Over-frequency, Under-frequency
3.6.3 Checking the parameters
The designer should have set all the necessary parameter in each controller during the design phase. However, DEIF
recommends that you check that these are suited to the actual site conditions.
To check the parameters for each controller:
1. Connect to the controller using PICUS.
2. Under Configure > Parameters, open each parameter menu and check each of the parameters. Adjust these if
necessary.
3. Write the new parameters to the controller.
CAUTION
Think carefully before adjusting any parameters set by the designer. If necessary, contact the designer for
permission to change the parameters and/or to clarify the design intent.
See the Designer's handbook for more information.
PPU 300 Commissioning guidelines 4189341106 UK