1.2 Specifications
1.2.1 General Specifications
Item Specifications
Operating temperature
-20 to +60°C
Storage temperature
-40 to +80°C
Operating humidity
595%
No condensation
Storage humidity
595%
No condensation
Work environment
No corrosive gas
Installation location
In a control box
Pollution degree
2
Ingress protection
(IP ratings)
IP20
EMC (electromagnetic
compatibility)
Refer to Chapter 7 for more information.
Vibration resistance
Tested with:
5 Hz f 8.4 Hz, constant amplitude 3.5 mm
8.4 Hz f 150 Hz, constant acceleration 1 g
Duration of oscillation: 10 sweep cycles per axis on each direction of the three
mutually perpendicular axes
International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc)
Shock resistance
Tested with:
Half-sine wave
Strength of shock: 15 g peak value, 11 ms duration
Shock direction: The shocks on each direction per axis, of the three mutually
perpendicular axes (for a total of 18 shocks)
International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea)
Safety
Conforms to IEC 61131-2, UL508
Ambient air
temperature-
barometric
pressure-altitude
Operating: 1080 ~ 795hPa (-1000 ~ 2000 m)
Storage:1080 ~ 660hPa (-1000 ~ 3500 m)