AS Series Module Manual
1- 6
1.2.2 EMS Standards
1.2.2.1 EMI
Port Frequency Range Level (Normative) Reference Standard
Enclosure port
(radiated)
(measured at a
distance of 10
meters)
30-230 MHz 40 dB (μV/m) quasi-peak
IEC 61000-6-4
230-1000 MHz 47 dB (μV/m) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79 dB (μV) quasi-peak
66 dB (μV) average
0.5-30 MHz
73 dB (μV) quasi-peak
60 dB (μV) average
1.2.2.2 EMS
Environmental
Phenomenon
Reference Standard Test Test Level
Electrostatic
Discharge
IEC 61000-4-2
Contact ±4 kV
Air ±8 kV
Radio Frequency
Electromagnetic Field
Amplitude
Modulated
IEC 61000-4-3
80% AM,
1 kHz
sinusoidal
2.0-2.7 GHz 1 V/m
1.4-2.0 GHz 3 V/m
80-1000 MHz 10 V/m
Power Frequency
Magnetic Field
IEC 61000-4-8
60 Hz 30 A/m
50 Hz 30 A/m

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL

Related product manuals