AS Series Module Manual
13-42
_13
13.6
Module Status Codes
The following error codes identify possible errors when the AS04SIL module as a communication module is installed on
the right side of the CPU module or RTU module.
Error
Code
Description Solution
16#1605
Hardware failure
Install a new AS04SIL or contact the factory.
16#1606
24VDC power supply is not sufficient
and then recovered from low-voltage
for less than 10 ms.
Check whether the 24 V power supply to the module is
normal.
Error
Code
Description Solution
16#1800
Error occurs in IO-Link Master
See section 13.5 for more information.
16#1801
Error occurs in IO-Link device
See section 13.5 for more information.
16#1802 No external power supply
Check the external power supply
16#1803
Error in the download of IO-Link
device mapping tables
Redownload the configuration by the software
16#1804
Failure to switch the process data
parameter set
Check if the connected device is the same as that configured in
the software.
16#1805
Error occurs in the communication
port 1 of IO-Link connection
1. Cut the external power off for 3 seconds and power-on
again
2. Download the configurations again
16#1806
Error occurs in the communication
port 2 of IO-Link connection
16#1807
Error occurs in the communication
port 3 of IO-Link connection
16#1808
Error occurs in the communication
port 4 of IO-Link connection
16#1809
Error occurs in scan device and
force to stop scanning
1. Cut the external power off for 3 seconds and power-on
again
2. Scan all devices again

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL

Related product manuals