Page #596 background imageLoading...
Page #596 background image
Chapter 13 IO-Link Communication Module AS04SIL
13-41
13
IO-Link
Event
Codes
Type
Event Solution
Source
Warning Error
Notifica-
tion
IO-Link
Master
IO-Link
Device
16#8CA8
V
Device power supply
voltage under-run L+
(<9V)
Check the external power
supply
V
16#8CA9
V
Illegal device ID
Check device
specifications
V
16#8CAA
V
HWCONFIG configured
process data exceeding
the IO-Link process
data range
Check device
specifications
V
16#8CAB
V
IO-Link process data
exceeding HWCONFIG
configured process
data range
Scan the device and
download the configuration
again
V
16#8CAC
V
Data storage error
Contact the factory
V
0xFF21
V
New connected device
V
0xFF22
V
Device disconnected
Check installation
V
0xFF23
V
Data storage
identification mismatch
Set the Data Storage
access locked and set it to
backup / restore and then
backing up data according
to actual placement.
V
0xFF24
V
Data storage not
sufficient
Check device
specifications
V
0xFF25
V
Data storage parameter
access denied
Check device
specifications
V

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL

Related product manuals