Chapter 3 Analog Input Module AS04/08AD-A
3- 9
3_
CR# Name Description
Atr. Defaults
37
The maximum scale
range for channel 4
value is 20 mA and the minimum value is 4 mA.
Note: You can use PLC instruction DSCLP
(API0217) and set SM685 to ON to use floating-
point operations when a conversion range needs to
edit.
10.0
38
201 Instruction Set
Instructions for peak values
16#0101: record the peak value again for channel
1
16#0102: record the peak value again for channel
2
16#0104: record the peak value again for channel
3
16#0108: record the peak value again for channel
4
16#010F: record the peak values again for
channels 14
16#0201: enable recording for channel 1
16#0202: enable recording for channel 2
16#0204: enable recording for channel 3
16#0208: enable recording for channel 4
16#020F: enable recording for channels 1–4
16#0211: disable recording for channel 1
16#0212: disable recording for channel 2
16#0214: disable recording for channel 3
16#0218: disable recording for channel 4
16#021F: disable recording for channels 1–4
16#0502: restore default settings
W 0
210
The maximum peak
value for channel 1
Integer format; the maximum peak value for analog
inputs
R
0
211
The maximum peak
value for channel 2
0
212
The maximum peak
value for channel 3
0
213
The maximum peak
0