Chapter 3 Analog Input Module AS04/08AD-A
3- 13
3_
CR# Name Description
Atr.
Defaults
percentage
41
Channel Sampling Cycle
(Sampling/Integration
Time)
0: 2 ms
1: 4 ms
2: 10 ms
3: 15 ms
4: 20 ms
5: 30 ms
6: 40 ms
7: 50 ms
8: 60 ms
9: 70 ms
10: 80 ms
11: 90 ms
12: 100 ms
R/W
0
42 Channel Alarm Setup
0: open channel alarm
1: close channel alarm
bit0: channel 1
bit1: channel 2
bit2: channel 3
bit3: channel 4
bit4: channel 5
bit5: channel 6
bit6: channel 7
bit7: channel 8
0: warning
1: alarm
bit8: error in the power supply
bit9: error in the module hardware
bit10: error in calibration
R/W
0
43
The minimum scale range
for channel 1
When the format is set to integer in
HWCONFIG, the scale range is invalid.
For analog-digital modules, it is much more
R
-10.0 44
45 The minimum scale range

Table of Contents