3_
CR# Name Description
Atr.
Defaults
201 Instruction Set
Instructions for peak values
16#0101: record the peak value again for
channel 1
16#0102: record the peak value again for
channel 2
16#0104: record the peak value again for
channel 3
16#0108: record the peak value again for
channel 4
16#010F: record the peak values again for
channels 1-4
16#0201: enable recording for channel 1
16#0202: enable recording for channel 2
16#0204: enable recording for channel 3
16#0208: enable recording for channel 4
16#020F: enable recording for channels 1–4
16#0211: disable recording for channel 1
16#0212: disable recording for channel 2
16#0214: disable recording for channel 3
16#0218: disable recording for channel 4
16#021F: disable recording for channels 1–4
16#0502: restore default settings
W
0
210
The
maximum peak value
for channel 1
Integer format; the maximum peak value for
analog inputs
R
0
211
The maximum peak value
for channel 2
0
212
The maximum peak value
for channel 3
0
213
The maximum peak value
for channel 4
0
214
The maximum peak value
for channel 5
0
215
The maximum peak value
for channel 6
0