EasyManuals Logo
Home>Delta>Control Unit>AS Series

Delta AS Series Manual

Delta AS Series
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
AS Series Module Manual
4- 4
_4
Digital-to-Analog
Conversion
Voltage Output
Output Impedance
≧1 kΩ ≧500 Ω
Digital-to-Analog Conversion Current Output
Rated Output Range 0 mA–20 mA 4 mA–20 mA
Conversion Range
K0
~
K32000
Hardware Output Range -0.2 mA to +20.2 mA 3.8 mA–20.2 mA
Error Rate
(Room Temperature)
±0.2%
Error Rate
(Full Temperature Range)
±0.5%
Linearity Error (Room
Temperature)
±0.03%
Linearity error (Full
Temperature Range)
±0.03%
Hardware Resolution 12 bits
Output Impedance
≦550 Ω