Chapter 5 CANopen Operation Mode ASDA A2-E
5-18 Revision April, 2015
5.9 Limit Position Handling Procedure
5.9.1 Description
Drive will switch to Quick-Stop status while traveling to the position of positive or
negative limit sensors, and it can be handled by the following procedures.
5.9.2 Operation Procedures
1. The servo panel will show the alarm while sensors are close to the positive or
negative limit. The motor is controlled by a deceleration slope to stop and it is at
Quick-Stop status. The drive will keep in servo-on status but will not accept the
further motion command.
2. Set Controlword:6040hto 0x8F for fault reset and clearing the alarm displayed
on the panel.
3. Set Controlword:6040hto 0x1F/0x0F for Operation Enabled, and then the servo
can accept the motion command again.
4. For a motor at its limit position, there must be a command which can drive the motor
to the backward direction. Or the alarm will be triggered again while the motor starts
moving.