Chapter 6  Control Modes of Operation  ASDA-B2 
6-26     Revision May, 2018 
Time Domain 
 
 
 
 
   
The bigger KVP value cause 
higher bandwidth and shorten the 
rising time. However, if the value 
is set too big, the phase margin 
will be too small.  
To steady-state error, the result 
is not as good as KVI. But it 
helps to reduce the dynamic 
following error. 
The bigger KVI value cause greater low-
frequency gain and shorten the time the 
steady-state error returns to zero. 
However, the phase margin will 
dramatically decrease as well.  
To steady-state error, it is very helpful but 
shows no benefit to dynamic following 
error. 
If the KVF value closes to 1, the 
feed forward compensation will be 
more complete and the dynamic 
following error will become 
smaller. However, if the KVF 
value is set too big, it would cause 
vibration.