8 Commissioning
Commissioning with the commissioning software
Installation and Operation Manual for Solar Power Inverter M70A EU V1.1 EN 2020-02-20
96
Error message and cause of error Error correction
Error event
"Wrong country ID setting! Please check your country ID!"
("Invalid country ID. Please check the RS485 connection.")
Cause of error
Fewer inverters were found when scanning the RS485 ring than specied in the Inv num
text box.
1
2
► Check whether the entry in the
Country-ID text box is correct
(1). Change the value if neces-
sary.
► To nish, click on the Set
Country button (2).
Error event
"Time Sync failed."
(German: "Synchronisierung der Uhrzeit fehlgeschlagen.")
Cause of error
Time synchronization failed.
1
► Check the time on the PC.
► To nish, click on the Sync
time button (1).