Chapter 4 Parameters|VFD-VL
4-54
02-37
Check Torque Output Function
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0 Enable
1
Disable
When the drive receives the operation signal, the drive will check if there is torque output.
When this function is enabled, it will release mechanical brake after confirming that there is
torque output.
02-31
06-31
06-31=1
06-31=0
02-37=0
02-37=1
operation command
enable drive function
(setting 40)
drive ready is finished
Turn on delay of
magnetic contactor
between drive and
motor
no-load current>70%*05-05
(only valid in FOCPG mode)
output current>02-33
detection of phase
loss of drive output
is normal
mechanical brake
release(setting 12)