CT100 inverter Detailed instructions of function parameters
96
Figure 6-1 Constant ACC/DEC curve
1: S curve (reserved)
Terminal characteristic
selection after power on
When the run command selection (F00.01) is the terminal control, the system will
automatically detect the status of the running terminal after power on.
0: run command is invalid
After power on, the inverter remains in stop state and it will not receive the
terminal run command. If you need to run the inverter, all the terminal run
commands should be cleared and then enable the terminal run command.
1: run command is valid
After power on, the inverter receives the terminal run command immediately.
0: no actuation
1: actuation
The inverter can run automatically when power on again after power off. Please
use this function with caution.
Power off restart waiting
time
Setting range: 0.0 ~
3000.0s
If the inverter is running before power off, it will run automatically after power off
restart waiting time (F02.09) after power failure.
0: decelerate to stop
Decelerate to stop according to the set DEC time.
1: coast to stop
The inverter immediately blocks the pulse output and the load coasts to stop in
accordance with the mechanical inertia.
Setting range: 0.0~2000.0s
When the inverter transforms between forward running and reverse running, the
running frequency will drop to the starting frequency (F02.02) at first and then
maintain the dead time of FWD/REV (F02.11). After the time, the inverter