CT100 inverter Function parameters
76
Function
code
Name
Detailed instruction of
parameters
Min. unit
Default
value
Modify
No.
F08.07
Overcurrent
stall protection
current
50200%
1%
G type
160%
P type
120%
F08.08
Overcurrent
stall frequency
decreasing ratio
0.0050.00Hz/s
0.01Hz/s
10.0Hz/s
F08.09
Overcurrent
stall actuation
selection
0: always valid
1: invalid at constant speed
1
0
F08.10
Frequency
decreasing
point at sudden
power loss
70.0110.0% (standard bus
voltage)
0.1%
80.0%
F08.11
Frequency
decreasing ratio
at sudden
power loss
0.00Hz F00.06 (Max.
frequency)
0.01Hz
0.00Hz/s
F08.12
Input phase
loss protection
0: disabled
1: enabled
1
1
F08.13
Output phase
loss protection
0: disabled
1: enabled
1
1
F08.14
Automatic reset
times
03
1
0
F08.15
Automatic reset
interval
0.1100.0s
0.1s
1.0s