CT100 inverter Function parameters
84
Function
code
Name
Detailed instruction of
parameters
Min. unit
Default
value
Modify
No.
F12.02
Data check
0: no check (N, 8,1) for RTU
1: even check (E, 8,1) for
RTU
2: odd check (O, 8,1) for RTU
3: no check (N, 8,2) for RTU
4: even check (E, 8,2) for
RTU
5: odd check (O, 8,2) for RTU
1
1
F12.03
Response delay
0200ms
1ms
5
F12.04
Communication
timeout
detection time
0.0 (invalid), 0.1100.0s
0.1s
0.0s
F12.05
Communication
timeout error
handling
0: alarm and coast to stop
1: no alarm and continue
running
2: no alarm and stop
according to stop mode
(communication mode is
valid)
3: no alarm and stop
according to stop mode (all
control modes are valid)
1
1
F12.06
Communication
processing
actuation
selection
LED ones
0: write with response
1: write without response
LED tens
0: set value unsaved after
power off
1: set value saved after
power off
0x01
0x00
F13 Group Auxiliary functions
F13.00
Jogging
frequency
0.00 F00.06 (Max.
frequency)
0.01Hz
5.00Hz
F13.01
Jogging running
ACC time
0.13000.0s
0.1s
20.0S