CT100 inverter Function parameters
85
Function
code
Name
Detailed instruction of
parameters
Min. unit
Default
value
Modify
No.
F13.02
Jogging running
DEC time
0.13000.0s
0.1s
20.0S
F13.03
ACC time 1
0.13000.0s
0.1s
20.0S
F13.04
DEC time 1
0.13000.0s
0.1s
20.0S
F13.05
ACC time 2
0.13000.0s
0.1s
20.0S
F13.06
DEC time 2
0.13000.0s
0.1s
20.0S
F13.07
ACC time 3
0.13000.0s
0.1s
20.0S
F13.08
DEC time 3
0.13000.0s
0.1s
20.0S
F13.09
Emergency
stop DEC time
(reserved)
0.13000.0s
0.1s
1.0s
F13.10
FDT level
detection value
0.00F00.06 (Max.
frequency)
0.01Hz
50.00Hz
F13.11
FDT lag
detection
0.0100.0% (FDT level)
0.1%
5.0%
F13.12
Frequency
arrival detection
amplitude
0.0 100.0% (Max.
frequency)
0.1%
0.0%
F13.13
Droop control
0.0010.00Hz
0.01Hz
0.00Hz
F13.14
Braking
threshold
voltage
115.0140.0% (standard
bus voltage) (380V)
0.1%
130.0%
115.0140.0% (standard
bus voltage) (220V)
0.1%
120.0%
F13.15
Overmodulation
function
0: invalid
1: valid
1
0
F13.16
Running mode
of cooling fan
0: normal running mode
1: keep running after power
on
1
0