Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 141
Table 26. Environmental and Safety (Continued)
BladeUPS 12 Model
BladeUPS 12i
Model BladeUPS 8 Model
BladeUPS 5.0
Model
Leakage Current <3.5 mA
Communication DB-9: 1200–19200 baud
Table 27. Battery
UPS Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
Configuration
(40) 12V, 5 Ah
(20) 12V, 5Ah
(5.0 kW only)
(20) 12V, 9 Ah (40) 12V, 9 Ah (60) 12V, 9 Ah (80) 12V, 9 Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid
Monitoring Advanced monitoring for earlier failure detection and warning
Charging (in
minutes)
8–10 times the discharge time
NOTE Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 28. Standalone UPS Battery Runtimes at Full/Half Load (in Minutes)
Model kW
UPS Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
BladeUPS 12 12/6 4.7/13.6 9.5/27 17/42 27/60 34/76
BladeUPS 12i 12/6 4.7/13.6 9.5/27 17/42 27/60 34/76
BladeUPS 8 8/4 8.7/23 17.7/41.5 27.9/65.5 43.0/94.1 54.7/120
BladeUPS 5.0
Single battery
string
5.0/2.5 6.2/16.1 21.7/45.8 37.2/80.1 59.2/128 79.0/175
BladeUPS 5.0
Two battery
strings
5.0/2.5 18.5/36.2 33/68.1 51.7/109.4 73/157.4 94.4/203.5
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 29. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity)
Number of
UPSs kW
UPS Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
2
24/12 4.7/13.6 9.5/27 17/42 27/60 34/76
3 36/18 4.7/13.6 9.5/27 17/42 27/60 34/76
4
48/24 4.7/13.6 9.5/27 17/42 27/60 34/76
Specifications