142 Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Table 29. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity) (Continued)
Number of
UPSs kW
UPS Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
5
60/30 4.7/13.6 9.5/27 17/42 27/60 34/76
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 30. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes with N+1)
Number of
UPSs kW
UPS Internal
Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
2 12/6 14/30 27/56 42/89 60/128 76/165
3
24/12 8.7/23 18/42 28/66 43/94 55/120
4
36/18 7.3/20 15/37 24/57 38/82 48/105
5
48/24 6.7/19.2 13/34 23/54 35/77 44/98
6
60/30 6.2/18.4 13/33 22/52 33/74 42/94
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Specifications