Appendix
10/10 MN05003003Z-EN
98
CAN(open)/easyNet
Transfer rate kBit/s 10, 20, 50, 100, 125, 250, 500
Default: 125
Potential isolation from inputs/outputs/power supply
yes
Bus termination resistor
120 O or EASY-NT-R plug (incl. bus terminating resistor 120 O)
Terminals
2 x RJ45, 8pole
CAN(open) operating mode:
– Station Number max. 126
–PDO type
Asynchronous, cyclic, acyclic
– Device profile
to DS301V4
easyNet mode:
– Station Number max. 8
Power supply
Rated voltage
Nominal value V DC, (%) 24, ( –15, +20)
Permissible range V DC
20.4 to 28.8
Residual ripple %
F 5
Input current at 24 V DC, typical mA
140
Voltage dips, IEC/EN 61131-2 ms
10
Power loss at 24 V DC, typical W
3.4
Inputs
Digital inputs
Number 12
Inputs that can be used for analog signals
I 7,8,11,12
Inputs that can be used for pulse signals
(High-speed counters)
I 1,2,3,4
Inputs for interrupt generation
I 1,2,3,4
Status indication
LC display
Potential isolation
from power supply, PC interface No
Between each other
No
from the outputs, to CAN interfaces
Yes
Rated voltage
Nominal value V DC 24
At signal ”0”
I1 to I6 and I9 to I10 V DC < 5
I7, I8, I11, I12 V DC
< 8
At signal ”1”
I1 to I6 and I9 to I10 V DC > 15
I7, I8, I11, I12 V DC
> 8
Input current on “1” signal (at 24 V DC)
I1 to I6, I9 to I10 mA 3.3
I7, I8, I11, I12 mA 2.2