Chapter 6—Motor Protection
116 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Application Configuration
Basic Parameters
Application dependent parameters need to be configured so
that the monitoring and protection functions can be
implemented.
The C445UM Monitoring User Interface and Power Xpert
inControl software tool both walk users through an easy
Setup Wizard for these parameters.
Table 24. Basic Parameters
Notes
1
These values may change depending on MM selection.
2
These values may change depending on MM use.
Advanced Parameters
Application dependent parameters are required for some
advanced applications. Users must set PT or CT Ratios if
external CTs or PTs are used. Additionally, users who want
to utilize motor torque and efficiency monitoring should set
Motor Rated Speed and Motor Rated Stator Resistance for
higher accuracy.
Table 25. Advanced Parameters
Parameter Units Increment Minimum Maximum Default Notes
FLA Motor1 amps 1 1
1
65535
1
101
1
ModBus Register = 900
FLA Motor2 amps 1 1
2
65535
2
101
2
ModBus Register = 901
Trip Class 1 5 40 5 ModBus Register = 1004
Rated Voltage volts 1 100 5000 480 ModBus Register = 903
HP Motor1 hp 1 1 500000 2000 ModBus Register = 909
HP Motor2 hp 1 1 500000 2000 ModBus Register = 911
Rated Frequency Hz 1 50 60 60 ModBus Register = 904
Phase Order ABC ACB ABC
Watts Motor1 watts
Watts Motor2 watts
Parameter Units Increment Minimum Maximum Default Notes
CT Ratio – Primary amps 1 1 1 Modbus Register = 918
CT Ratio – Secondary amps 1 1 1 Modbus Register = 919
PT Ratio Primary V 1 1 1 Modbus Register = 920
PT Ratio Secondary V 1 1 1 Modbus Register = 921
Motor Rated Speed Motor1 RPM 1 300 3600 1750 Modbus Register = 914
Motor Rated Speed Motor2 RPM 1 300 3600 1750 Modbus Register = 915
Motor Rated Stator Resistance ohms 1 1 0 280 Modbus Register = 917