EasyManua.ls Logo

Eaton Power Xpert C445 - Table 72. Input;Output Specifications; Table 73. PTC Specifications

Eaton Power Xpert C445
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A—Technical Data and Specifications
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 213
Table 72. Input/Output Specifications
Table 73. PTC Specifications
Description Specification
Relay Rating Relay Q1 / Q2 (from A – NO)
B300 Pilot Duty, R300 Pilot Duty
AC-15: 3 A at 120 Vac, 1.5 A at 240 Vac
DC-13: 0.22 at 125 Vdc, 0.1 at 250 Vdc, 2 A at 24 Vdc
Relay Q3 (from C – latching)
B300 Pilot Duty, R300 Pilot Duty
AC-15: 3 A at 120 Vac, 1.5 A at 240 Vac
DC-13: 0.22 at 125 Vdc, 0.1 at 250 Vdc, 1.5 A at 24 Vdc
Relay Q3 (from C – non-latching)
B300 Pilot Duty, R300 Pilot Duty
AC-15: 3 A at 120 Vac, 1.5 A at 240 Vac
DC-13: 0.22 at 125 Vdc, 0.1 at 250 Vdc, 2 A at 24 Vdc
The Q3 normally closed relay contacts should not be used for motor contactor control
AC Field Input
1
IEC 61131-2 Type 1 Digital Input
Off State: 0 Vac to 20 Vac
On State: 79 Vac to 132 Vac
Max. ON current: 15 mA
DC Field Input IEC 61131-2 Type 1 Digital Input
Off State: 0 Vac to 5 Vdc
On State: 15 Vdc to 30 Vdc
Max. ON current: 15 mA
Mandatory Short Circuit
Protection for Auxiliary Contacts
(relay outputs)
6 A Class gG fuse (IEC 60947-5-1)
Terminal Block Wiring capacity: 0.2 mm
2
(24 AWG) to 2.5 mm
2
(12 AWG)
Use only UL listed or recognized conductors. Copper wire rated 75C (75°C UC wire) for
all field wiring terminals and main overload conductor wiring.
Description Specification
Standard EN 60947-8/A1:2006 “Mark A Control Unit”
Compatible Thermal Detectors MARK A type (abrupt characteristic change) as described in EN 60947-8/A1:2006
Annex A wired in series
Terminals Marked T1 & T2.
0.2 mm
2
(24 AWG) to 2.5 mm
2
(12 AWG)
Cold Resistance <= 1500 ohms
Measuring Voltage T1-T2 <= 2.5 V for resistance <= 1330 ohms
<= 7.5 V for resistance <= 4 kohms
<= 9.0 V open circuit
Temperature Rise Response 3600 ohms ±10%
Over Temperature Reset 1500 ohms ±10%
Short Circuit Response Between 10 and 20 ohms
Short Circuit Reset Between 20 and 40 ohms
Wire Break Response 20 k to 40 kohms
Isolation See Table 82.