Chapter 6—Motor Protection
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 127
Example #6
Mains voltage does not return above Voltage Return Level
setting in <VL Long Time. Contactor does not re-close and
voltage loss restart has ended. User must manually go
through restart sequence once voltage returns.
Figure 117. Example #6: Long-Time—Mains Voltage Does Not Return Before Long Time Expires
Protection and Monitoring
The C445 Base Control Module monitors several parameters
for motor protection. There are several ways to monitor
parameters.
The Monitoring User Interface
Power Xpert inControl
Over the communication network of choice
Web pages
Trip Protection will stop the motor if select parameter values
exceed set limits. There are data log records created and
stored in non-volatile memory. These snapshots can be
analyzed to determine the cause of failure. After a trip has
occurred, a reset feature may be configured to attempt to
reset the motor.