Chapter 6—Motor Protection
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 139
High Power
The High Power protection monitors the kW consumed
(supply side) by the load and will trip the motor if the
measured value exceeds the set threshold. The High Power
protection is active when the motor is in the Running state.
The rated power is calculated from the rated HP input by
the user.
Table 51. High Power
Peak Demand Alarming
A utility company’s bill is based on consumption (kWHr) and
more typically on peak demand in the last month. In the US
demand is typically calculated as the average kW in a 15
minute window. The peak demand is simply the maximum
value of the calculated demand. Industrial users may have
rather sophisticated load shedding and demand response
processes running at the feeder level or higher.
The C445 will provide a simplified demand warning system
that will provide the current demand estimate, a resettable
peak demand (with date and time stamp) stored in
nonvolatile memory, and a demand warning threshold. The
time window for demand calculation will be adjustable to
provide for more flexibility.
Table 52. Peak Demand
Fault
Code Modbus
Fault Action Delay (Seconds)
Protection Action Units Min. Max. Default Min. Max. Default Modbus
15 High Power Fault Trip 1046 % –200 200 110 1 60 20 1048
Fault Warning 1047 % –200 200 110 1 60 2 1079
Fault
Code Modbus
Fault Action
Protection Parameter Units Min. Max. Default
Peak Demand Demand Window Duration 1054 Minutes 1 240 15
Peak Demand Warning Threshold 1052 Watts 0
Peak Demand Watts
Present Demand Watts
Demand Timestamp Unix