Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 289
Instance Attributes
Sr. No. ID Description Access Rule Data Type Remarks
1 1 (0x1) Status Get DWORD 01 00 00 00
2 2 (0x2) Configuration Capability Get DWORD F4 00 00 00
3 3 (0x3) Configuration Control Get / Set DWORD 02-dhcp, 0- static
4 4 (0x4) Physical Link Get STRUCT of
Path Size UINT 0
Path Padded EPATH 0
5 5 (0x5) Interface Configuration Get / Set Struct of:-NV
IP Address UDINT 192.168.1.254
Network Mask UDINT 255.255.255.0
Gateway Address UDINT 192.168.1.1
Name Server UDINT 0
Name Server 2 UDINT 0
Domain Name STRING 0
6 6 (0x6) Host Name Get / Set STRING 0
7 8 (0x8) TTL Value Get USINT 1
8 9 (0x9) Multicast Configuration Get Struct of:
Alloc Control USINT 0
Reserved USINT 0
Number of Mcast UINT 0x20
Starting Multicast Address DWORD 80 20 C0 EE
9 10 (0xA) SelectAcd Set / Get BOOL 1
10 11 (0xB) Last Conflict Detected Set / Get Struct of:
ACD activity USINT 0
Remote MAC Array of 6 USINT 0
ARP PDU Array of28 USINT 0
11 13 (0xD) Encapsulation Inactivity Timeout Set / Get UINT 0 = Disable
1-3600 = timeout in seconds
Default = 120
Table 116. Ethernet Link Object—Class 0xF6 (246)
Class Services
Service
Code Service Name
0x0E Get Attribute Single
0x01 Get Attributes All
Instance Services
Service
Code Service Name
0x0E Get Attribute Single
0x10 Set Attribute Single
0x01 Get Attributes All
Table 115. TCP/IP Object—Class 0xF5 (245), continued