Appendix COptional Communication Cards
290 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Class Attributes
Sr. No. ID Description Access Rule Data Type Remarks/Default
1 1 (0x1) Revision Get UINT 3
2 2 (0x2) Max Instance Get UINT 2
3 3 (0x3) Number of Instances Get UINT 2
4 4 (0x4) Optional Attribute List Get Struct of:
Number of Attributes UINT 03 00 04 00
Array of Attributes Array of UINT 07 00 08 00 09 00 0A 00
5 6 (0x6) Maximum ID Class Attribute Get UINT 7
6 7 (0x7) Maximum ID Instance Attribute Get UINT 0A
Instance Attributes
Number of instances: 2
Sr. No. ID Description Access Rule Data Type Remarks/Default
1 1 (0x1) Interface Speed Get UDINT 64 00 00 00
2 2 (0x2) Interface Flags Get DWORD 2D
3 3 (0x3) Physical Address Get ARRAY of 6
USINTs
Range of 00:D0:AF:1A:00:00 to
00:D0:AF:1D:D0:FF
4 6 (0x6) Interface Control Get/Set Struct of:
Control Bits WORD 1
Forced Interface Speed UINT 0A (10) or 64 (100)
5 7 (0x7) Interface Type Get USINT 2
6 8 (0x8) Interface State Get USINT 1
7 9 (0x9) Admin State Set USINT As per EIP Specs
8 10 (0xA) Interface Label Get Short String “Port 1” for Instance 1 and “Port 2” for
Instance 2
Table 116. Ethernet Link Object—Class 0xF6 (246), continued

Table of Contents

Other manuals for Eaton Power Xpert C445