Appendix C—Optional Communication Cards
276 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
5 5 (0x5) Get/Set UDINT Motor Rated Watts Motor2 Motor Rated Watts Run2
6 6 (0x6) Get/Set UINT Motor Rated Speed Motor1 Motor Rated Speed RPM Run1
7 7 (0x7) Get/Set UINT Motor Rated Speed Motor2 Motor Rated Speed RPM Run2
8 8 (0x8) Get/Set UINT Rated Freq Motor rated frequency in Hz
9 9 (0x9) Get/Set UINT Motor Rated Efficiency Motor rated efficiency in percentage
10 10 (0xA) Get/Set INT Motor Rated PF (scaled by 100) Motor rated power factor in percentage
11 11 (0xB) Get/Set USINT Motor Rated Service Factor Motor Rated Service Factor
12 12 (0xC) Get/Set UINT Motor Rated Stator Resistance (Scaled
x1000)
Motor Rated Stator Resistance (Scaled x1000)
13 13 (0xD) Get UDINT Motor Rated Hp Active (Scaled by 100) Motor Rated Hp Active
14 14 (0xE) Get UINT Motor Rated Speed Active Motor Rated Speed RPM active
15 15 (0xF) Get UDINT Motor Rated Watts Active Motor Rated Watts Active
Table 105. Operation Mode Object—Class 0x9F (159)
Class Services
Service
Code Service Name
0x0E Get Attribute Single
Instance Services
Service
Code Service Name
0x0E Get Attribute Single
0x10 Set Attribute Single
Class Attributes
Sr. No. Attribute ID Access Rule Data Type Name Attribute Description
1 1 (0x1) Get UINT Revision Revision of this object
2 2 (0x2) Get UINT Max Instance Maximum instance number of an object currently created
in this class level of the device.
3 3 (0x3) Get UINT Number of Instances Number of object instances currently created at this class
level of the device.
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
1 1 (0x1) Get/Set USINT Used to select the desired control profile
(soft reset required)
Used to select the desired control profile (soft reset
required)
2 2 (0x2) Get/Set UINT Delay before control fault is issued (in
10ms)
Delay before control fault is issued (in 10ms)
3 3 (0x3) Get/Set UINT Interlocking time between contactor
direction changes (in 0.01sec)
Interlocking time between contactor direction changes (in
0.01sec)
4 4 (0x4) Get/Set UINT Switching time between contactor speed
changes (in 0.01sec)
Switching time between contactor speed changes (in
0.01sec)
5 5 (0x5) Get/Set UINT Settling time delay when a network
contactor is used. (in 10ms)
Settling time delay when a network contactor is used. (in
10ms)
6 6 (0x6) Get/Set UINT Maximum star (wye) wiring time (in
0.1sec)
Maximum star (wye) wiring time (in 0.1sec)
7 7 (0x7) Get/Set BOOL Enables MCCB Feeder actuation control Enables MCCB Feeder actuation control
8 8 (0x8) Get/Set UINT Output pulse width for MCCB actuation (in
1.0 ms)
Output pulse width for MCCB actuation (in 1.0 ms)
Table 104. Motor Info Object—Class 0x9B (155), continued