Eaton Power Xpert C445 - Table 98. Control Supervisor Object-Class 0 X29

Eaton Power Xpert C445
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix COptional Communication Cards
264 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Table 98. Control Supervisor Object—Class 0x29 (41)
Class Services
ID Service Requirements
0x0E Get Attribute Single
Instance Services
ID Service
0x0E Get_Attribute_Single
0x10 Set_Attribute_Single
0x05 Reset Service Type 0
Class Attributes
Sr. No. ID Access Rule Data Type Name Description Default Range
1 1 (0x1) Get UINT Revision 1
2 2 (0x2) Get UINT Max Instance 1
3 3 (0x3) Get UINT Number of
Instances
1—
Instance Attributes
Sr. No. ID Access Rule Data Type Description
1 3 (0x3) Set BOOL Run1 Run/Stop Event Matrix 0 0 – 1
2 4 (0x4) Set BOOL Run2 Run/Stop Event Matrix 0 0 – 1
3 5 (0x5) Set BOOL NetCtrl Requests Run/Stop control to be local or from network.
0 = Local Control
1 = Network Control
Note that the actual status of Run/Stop control is reflected in
attribute 15, CtrlFromNet.
00 1
4 7 (0x7) Get BOOL Running1 1 = (Enabled and Run1) or (Stopping and Running1) or
(Fault_Stop and Running1)
0 = Other state
00 1
5 8 (0x8) Get BOOL Running2 1 = (Enabled and Run1) or (Stopping and Running1) or
(Fault_Stop and Running1)
0 = Other state
00 1
6 9 (0x9) Get BOOL Ready 1 = Ready or Enabled or Stopping
0 = Other state
00 1
7 11 (0xB) Get BOOL Warning 1 = Warning (not latched)
0 = No Warnings present
00-1
8 12 (0xC) Set BOOL FaultRst 0
R1 = Fault Reset
0 = No action
00 1
9 13 (0xD) Get UINT Fault Queue-1 A list of faults based on most recent. Duplicates are not
allowed. They are sorted by event with the newest at the top
of the queue.
10 15 (0xF) Get BOOL CtrlFromNet Status of Run/Stop control source.
0=Control is local
1=Control is from network
00 1
11 17 (0x11) Set BOOL CIP Force Fault
(Need
Dependent DCID
in BCM)
0
R1 = Force

Table of Contents