Appendix COptional Communication Cards
224 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
LED Status Indicators
The Ethernet Card includes indicators for the module status
(MS) and Network Status (NS). The Module Status Indicator
states are described in the table below.
Table 86. Module Status Indicator
Indicator State Summary Requirement
Steady Off No power If no power is supplied to device, the module status indicator shall be steady Off.
Steady Green Device operational If the device is operating correctly, the module status indicator shall be steady green
Flashing Green Standby If the device has not been configured, the module status indicator shall be flashing green.
Flashing Red Minor Fault If the device has detected a recoverable minor fault, the module status indicator shall be flashing red.
Steady Red Major Fault If the device has detected a non-recoverable major
fault, the module status indicator shall be steady red.
Table 87. Network Status Indicator
Indicator State Summary Requirement
Steady Off Not Powered, No IP
Address
The device is powered off, or is powered on but with no IP address configured (Interface Configuration
attribute of the TCP/IP Interface Object).
Flashing Green No Connections An IP address is configured, but no CIP connections are established, and an Exclusive Owner connection
has not timed out.
Steady Green Connected At least one CIP connection (any transport class) is established, and an Exclusive Owner connection has
not timed out.
Flashing Red Connection Time-out An Exclusive Owner connection for which this device is the target has timed out. The network status
indicator shall return to steady green only when all timed out Exclusive Owner connections are
re-established.
Steady Red Duplicate IP If the device has detected a non-recoverable major fault, the module status indicator shall be steady red.
Flashing Green
and Red
Self-test While the device is performing its power up testing, the module status indicator shall be flashing green
and red.