Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 261
Table 95. Connection Manager Object—Class 0x6 (6)
Class Services
Service
Code Service Name
0x0E Get Attribute Single
0x01 Get Attributes All
Instance Services
Service
Code
Service Name
0x0E Get Attribute Single
0x01 Get Attributes All
0x10 Set Attribute Single
0x02 Set Attributes All
0x4E Forward Close
0x52 Unconnected Send
0x54 Forward Open
0x5A Get Connection Owner
0x5B Large Forward Open
Class Attributes
Sr. No. Attribute ID Access Rule Data Type Name Attribute Description
1 1 (0x1) Get UINT Revision Revision of this object
2 2 (0x2) Get UINT Max. Instance Maximum instance number of an object currently created in this
class level of the device.
3 3 (0x3) Get UINT Number of Instances Number of object instances currently created at this class level of
the device.
4 4 (0x4) Get STRUCT Optional Attribute List List of optional instance attributes utilized in an object class
implementation.
5 6 (0x6) Get UINT Maximum ID Number Class
Attributes
The attribute ID number of the last class attribute of the class
definition implemented in the device.
6 7 (0x7) Get UINT Maximum ID Number Instance
Attributes
The attribute ID number of the last instance attribute of the class
definition implemented in the device.
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
1 1 (0x1) Set UINT Open Requests Number of Forward Open service requests received.
2 2 (0x2) Set UINT Open Format Rejects Number of Forward Open service requests which were rejected
due to bad format.
3 3 (0x3) Set UINT Open Resource Rejects Number of Forward Open service requests which were rejected
due to lack of resources.
4 4 (0x4) Set UINT Open Other Rejects Number of Forward Open service requests which were rejected
for reasons other than bad format or lack of resources.
5 5 (0x5) Set UINT Close Requests Number of Forward Close service requests received.
6 6 (0x6) Set UINT Close Format Requests Number of Forward Close service requests which were rejected
due to bad format.
7 7 (0x7) Set UINT Close Other Requests Number of Forward Close service requests which were rejected
for reasons other than bad format.
8 8 (0x8) Set UINT Connection Timeouts Total number of connection timeouts that have occurred in
connections controlled by this Connection Manager.