Appendix C—Optional Communication Cards
288 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Class Attributes
Sr. No. ID Description Access Rule Data Type Remarks/Default
1 1 (0x1) Revision Get UINT 1
2 2 (0x2) Max Instance Get UINT 2
3 3 (0x3) Number of Instances Get UINT 2
4 6 (0x6) Maximum ID Class Attribute Get UINT 9
5 7 (0x7) Maximum ID Instance Attribute Get UINT 7
6 8 (0x8) Entry Port Get UINT 2
7 9 (0x9) Port Instance Info Get Array of Struct of
Port Type UINT See Instance attribute
Port Number UINT See Instance attribute
Instance Attributes
Number of instances: 2
Sr. No. ID Description Access Rule Data Type Remarks/Default
1 1 (0x1) Port Type Get UINT 4
2 2 (0x2) Port Number Get UINT 1 or 2
3 3 (0x3) Link Object Get Struct of:
Path Length UINT 2
Link Path Padded EPATH 20 F5 24 01
4 4 (0x4) Port Name Get Short String Ethernet/IP Port (in ASCII)
7 7 (0x7) Port Number and Node address Get Padded EPATH Active IP address (in ASCII)
Table 115. TCP/IP Object—Class 0xF5 (245)
Class Services
Service
Code Service Name
0x0E Get Attribute Single
0x01 Get Attributes All
Instance Services
Service
Code Service Name
0x0E Get Attribute Single
0x10 Set Attribute Single
0x01 Get Attributes All
Class Services
Sr. No. ID Description Access Rule Data Remarks/Default
1 1 (0x1) Revision Get UINT 4
2 2 (0x2) Max Instance Get UINT 1
3 3 (0x3) Number of instances Get UINT 1
4 4 (0x4) Optional attribute list Get Array of UINT 04 00 08 00 09 00 0A 00 0B 00
5 6 (0x6) Maximum ID Class Attribute Get UINT
6 7 (0x7) Maximum ID Instance Attribute Get UINT 0B 00
Table 114. Port Object—Class 0xF4 (244), continued