Chapter 10—C445 Ground Fault Monitoring and Protection
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 211
Table 69. Pulse Detection Protection Parameterization
Fault
Code
Parameter Value
Action Modbus Units Frame Minimum Maximum Default
44 Fault Trip 1094 Amps C445XG-CT2 0.03 10.0 4
C445XG-CT3 0.03 10.0 4
C445XG-CT4 0.03 10.0 4
C445XG-CT7 0.03 10.0 4
Fault Trip Indication Only 1088
Fault Warning 1003 Amps C445XG-CT2 0.03 10.0 4
C445XG-CT3 0.03 10.0 4
C445XG-CT4 0.03 10.0 4
C445XG-CT7 0.03 10.0 4
C445XG-MOD C445XG-CT2 C445XG-CT3 C445XG-CT4 C445XG-CT7