Appendix C—Optional Communication Cards
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 265
Instance Attributes
Sr. No. ID Access Rule Data Type Description
12 101 (0x65) Get/Set BYTE Fieldbus Motor
Control
Device Bit Array
Bit 0: Run1
Bit 1: Run2
Bit 2: Reserved
Bit 3: Fault Reset
Bit 4: Reserved
Bit 5: Test Trip
Bit 6: Reserved
Bit 7: Reserved
13 102 (0x66) Get/Set BYTE Network Control
Word with
NetCtrl bit
Device Bit Array
Bit 0: Run1
Bit 1: Run2
Bit 2: Reserved
Bit 3: Fault Reset
Bit 4: NetCtrl
Bit 5: Test Trip
Bit 6: Reserved
Bit 7: Reserved
14 103 (0x67) Get/Set BYTE FieldBus Input
Feedback
Register
Bit 0: Network feedback input0
Bit 1: Network feedback input1
Bit 2: Network feedback input2
Bit 3: Network feedback input3
Bit 4: Network feedback input4
Bit 5: Network feedback input5
Bit 6: Network feedback input6
Bit 7: Network feedback input7
15 104 (0x68) Get WORD Packed Device
Status
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed
16 105 (0x69) Get BYTE Motor Control
Status
Bit 0: Running1
Bit 1: Running2
Bit 2: Remote or CtrlFromNet
Bit 3: Faulted/Tripped
Bit 4: Warning
Bit 5: Inhibited
Bit 6: Ready
Bit 7: AtRef or Up-To-Speed
Table 98. Control Supervisor Object—Class 0x29 (41), continued