Chapter 9C445 Logic Engine and Expansion I/O
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 161
RS_D—Reset Dominant Bi-Stable with Data Input
The RS_D function block performs as an RS function block with SET and RESET when
LOAD is FALSE. But, when LOAD is set to TRUE, DATA is copied to the output.
SET RESET DATA LOAD OUT (Previous) OUT
00x00 0
00x01 1
10x00 1
10x01 1
x011x 1
x001x 0
x1xxx 0
Parameter Data type Description
SET BOOL Set input
DATA BOOL Data input, will be copied to OUT when LOAD = TRUE
LOAD BOOL Load input for DATA
RESET BOOL Reset input
OUT BOOL Output