Appendix COptional Communication Cards
244 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
12 2 Current Average MOTOR_I_AVE_SCALED:
Average Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
14 2 Voltage L1-L2 LINE_V_LL_AB_RMS:
Phase A RMS Voltage L1-L2 (V)
16 2 Voltage L2-L3 LINE_V_LL_BC_RMS:
Phase B RMS Voltage L2-L3 (V)
18 2 Voltage L3-L1 LINE_V_LL_CA_RMS:
Phase C RMS Voltage L3-L1 (V)
20 2 Voltage Average LINE_V_LN_AVE_RMS:
Average RMS Voltage (V)
22 2 Digital Inputs Bits 0-7 = Inputs for the first digital input card
Bits 8-15 = Inputs for the second digital input card
24 2 Analog Inputs 1 Input word of data for an analog output card status
Input Instance 112 (0x70): Status, Current, Voltage, Trip with Analog and Digital Inputs
Length = 36 Bytes
Byte
Offset
Size
(bytes) Name Description
0 2 Device Status C445_DEVICE_STATUS
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed
2 2 Current L1 MOTOR_I_A_SCALED:
Phase A (L1) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
4 2 Current L2 MOTOR_I_B_SCALED:
Phase B (L2) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
6 2 Current L3 MOTOR_I_C_SCALED:
Phase C (L3) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
Input Instance 111 (0x6F): Status, Current, Voltage, Trip with Basic Analog and Digital Inputs, continued
Length = 26 Bytes
Byte
Offset
Size
(bytes) Name Description

Table of Contents