Appendix COptional Communication Cards
246 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Input Instance 113 (0x71): Status, Current, Voltage, Trip with Extended Analog and Digital Inputs
Length = 48 Bytes
Byte
Offset
Size
(bytes) Name Description
0 2 Device Status C445_DEVICE_STATUS
Bit 0: Faulted/Tripped
Bit 1: Warning
Bit 2: Output #1
Bit 3: Output #2
Bit 4: Input #1
Bit 5: Input #2
Bit 6: Input #3
Bit 7: Input #4
Bit 8: Running1
Bit 9: Running2
Bit 10: Remote or CtrlFromNet
Bit 11: Output #3
Bit 12: Reserved
Bit 13: Inhibited
Bit 14: Ready
Bit 15: AtRef or Up-To-Speed
2 2 Current L1 MOTOR_I_A_SCALED:
Phase A (L1) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
4 2 Current L2 MOTOR_I_B_SCALED:
Phase B (L2) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
6 2 Current L3 MOTOR_I_C_SCALED:
Phase C (L3) Motor Current Scaled.
Scaled by parameter “I Scale Factor.”
8 4 Trip Reason STATUS_TRIPPED_BITS
0x0000 0001 - under voltage
0x0000 0002 - over voltage
0x0000 0004 - Reserved
0x0000 0008 - ground current fault
0x0000 0010 - current phase loss
0x0000 0020 - current unbalance
0x0000 0040 - instantaneous over current
0x0000 0080 - jam
0x0000 0100 - PF deviation
0x0000 0200 - voltage phase loss
0x0000 0400 - voltage unbalance
0x0000 0800 - freq deviation fast
0x0000 1000 - freq deviation slow
0x0000 2000 - under current
0x0000 4000 - high power
0x0000 8000 - low power
0x0001 0000 - Reserved
0x0002 0000 - exceeds starts limit
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection