Appendix C—Optional Communication Cards
278 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
1 1 (0x1) Get/Set USINT Remote Modbus Address Remote Modbus Address
2 2 (0x2) Get/Set USINT Remote Modbus Baud Rate Remote Modbus Baud Rate
3 3 (0x3) Get/Set USINT Remote Modbus Parity and Stop Bits Remote Modbus Parity and Stop Bits
4 4 (0x4) Get/Set USINT Remote Modbus TX Mode Remote Modbus TX Mode
5 5 (0x5) Get/Set UINT Remote Modbus Communication Timeout Remote Modbus Communication Timeout
6 6 (0x6) Get/Set UINT Base Control Module USB Modbus
CommTimeout
Base Control Module USB Modbus CommTimeout
7 7 (0x7) Get/Set UINT User Interface USB Modbus
CommTimeout
User Interface USB Modbus CommTimeout
8 8 (0x8) Get/Set UINT Modbus Scan Data Modbus Scan Data
9 9 (0x9) Get/Set UINT Modbus Scan List Modbus Scan List
Table 107. Motor Monitoring Object—Class 0xA1 (161)
Class Services
Service
Code Service Name
0x0E Get Attribute Single
Instance Services
Service
Code Service Name
0x0E Get Attribute Single
0x10 Set Attribute Single
Class Attributes
Sr. No. Attribute ID Access Rule Data Type Name Attribute Description
1 1 (0x1) Get UINT Revision Revision of this object
2 2 (0x2) Get UINT Max Instance Maximum instance number of an object currently created
in this class level of the device.
3 3 (0x3) Get UINT Number of Instances Number of object instances currently created at this class
level of the device.
Instance Attributes
Sr. No. Attribute ID Access Data Type Attribute Name Attribute Description
1 1 (0x1) Get USINT Motor State (enum) Motor State (enum)
2 2 (0x2) Get UINT Speed (RPM) Speed (RPM)
3 3 (0x3) Get INT Torque Torque
4 4 (0x4) Get UINT Efficiency in percent Efficiency in percent
5 5 (0x5) Get USINT PTC Status PTC Status
6 6 (0x6) Get UDINT Number of Motor Starts Number of Motor Starts
7 7 (0x7) Get UINT Number of Contactor Operations During
Last Hour
Number of Contactor Operations During Last Hour
8 8 (0x8) Get/Set UDINT Number of Motor Starts User Number of Motor Starts User
9 9 (0x9) Get UDINT Number of Operating Seconds Number of Operating Seconds
10 10 (0xA) Get/Set UDINT Number of Operating Seconds (user) Number of Operating Seconds (user)
11 11 (0xB) Get UINT Last Measured Starting Time. Time to get
up to speed.
Last Measured Starting Time. Time to get up to speed.
12 12 (0xC) Get UDINT Motor Run Time Latest Run - How long the
motor was running last time.
Motor Run Time Latest Run - How long the motor was
running last time.
13 13 (0xD) Get UDINT Motor Run Time Total Motor Run Time Total
Table 106. Modbus Object—Class 0xA0 (160), continued